The Protec 2 way input/output interface is a loop powered input / output device providing 2 monitored inputs and two volt free changeover contacts. The contacts may be used to connect to ancillary equipment.
Loop protocol | Protec Algo-tec™ 6000 MX1 |
Loop isolator fitted | Yes, on board (consult Protec DEL2110 for details) |
Loop voltage range | 18 to 28V peak loop |
Number of loop addresses used | 2 maximum, user and build configurable |
24V Auxiliary input voltage range | 18 to 28V dc |
Environmental operational limits | -10 to 50ºC (maximum 95% RH no condensation or icing) |
Loop quiescent current (24V loop peak) | 1.6mA + zone end of line current + zone loading |
Loop alarm current (average) | 18mA |
Zone short circuit current (24V) | 26mA peak ± 2mA |
Zone end of line requirements (I/P 1 & I/P 2) | Resistive – 8.2k ±5% ¼W, Capacitive – 100μ F ±20% in series with 22Ω ±5% ¼W |
Input cabling requirements | Maximum cable resistance 6Ω per conductor Maximum cable capacitance 0.2μ F between cable conductors |
Monitored input end of line details | End of line resistor value 47kΩ 1/4W ±5% |
Monitored input short circuit threshold | Below 230Ω |
Monitored input fire threshold | Below 7.85kΩ |
Monitored input pre-alarm threshold | Below 32kΩ ( Input 3 only ) |
Monitored input open circuit threshold | Above 111kΩ |
Clean contact output details | 1 Single pole changeover rated for 2A maximum at 24V dc ( non inductive ) 1 Single pole changeover rated for 5A maximum at 230V ac ( non inductive ) |
Weight | 245g ( including din rail housing, no backbox, 4 way build ) |
LED Indicator | Use only high brightness LED (Protec stock code: NK 02-676-46) |
Datasheet Clique Aqui