The Protec Algo-Tec™ 6000 Local Control Module has been designed to allow easy integration of Protec Addressable Fire Detection systems into Houses in Multiple Occupancy and offers novel features to reduce false and nuisance alarms.
The unit effectively operates as a stand alone fire alarm control panel monitoring detectors and driving sounders in a zone. An automatic detector activation on the zone instigates a search timer to allow the cause of the alarm to be investigated, and dealt with locally, prior to signalling a full alarm to the building fire alarm system. The unit is loop powered and reports its status back to the master panel at regular intervals.
Operation
The device monitors the detection zone for activations, if one occurs the following decisions are taken.
If the mute button is pressed before the search time expires the fire signal to the host panel is delayed by up to 2 minutes. If the zone returns to normal within this time no further action is taken.
If the mute button is pressed prior to an activation an ‘isolated’ period of 15 minutes is instigated. If the mute button is pressed again during the ‘isolated’ period the device returns to normal.
An internal buzzer sounds 15 seconds prior to either the muted or the isolated period expiring.
If the mute button is pressed during the 15 second expiry period the original time-out of 2 or 15 minutes is re-set.
If the master panel has a fire activation the device can be programmed to activate the sounder outputs, this overrides any muted, or isolated state.
Protocol Protec | Algo-Tec™ 6000 |
Number of Addresses | 1 |
Loop Voltage Range | 18 to 28V |
Loop Powered | Yes |
Loop Standby Load | 0.7mA quiescent + detector zone load (500μA max) + (3mA if resistive EOL used) |
Loop Alarm Load (Max) | 5mA + detector zone load (12mA max) + sounder load (50mA max) |