O Protec Algo-Tec™ 6100 é um sistema interativo digital endereçável de detecção e alarme de incêndio, ideal para edifícios de pequeno e médio porte, como lojas, hotéis e escritórios. O painel de controle foi projetado e fabricado pela Protec em conformidade com EN 54-2 e 4. O painel de controle é adequado para montagem em superfície ou embutida com um gabinete de policarbonato moldado com acabamento em cinza tempestade.
| Rated Voltage | 100 to 240V ac rms |
| Rated Frequency | 50 to 60 Hz |
| Rated Current | 600mA rms |
| Working Voltage | 21.5 – 29V dc |
| Temperature Range | 0 – 40°C |
| Maximum Humidity | 85% Non-condensing |
| IP Rating | IP30 |
| Battery Type | 2 x 12V 3.3Ah sealed lead acid |
| Standby Load (Mains Fail Condition) | 22mA |
| Maximum Alarm Load (Mains Fail Condition) | 56mA panel 600mA loop 200mA conventional alarms (100mA per alarm output) 150mA auxillary 24V output 20mA fire-link |
| Display | Backlit liquid crystal display 4 lines of 20 characters |
| Digital Addressable Loops | 1 loop, with 192 address capacity Algo-Tec™ 6000PLUS Protocol |
| Total Loop Load | 600mA including all loop connected devices |
| Zones | 32 Zones, 16 with LED indication, plus general fire indicator |
| Integral Charger | 1A dc switch mode, temperature compensated |
| Integral Battery | 2 x 12V 3.3Ah sealed lead acid |
| Alarm Outputs | 2 monitored conventional sounder circuits (100mA per output maximum)Up to 192 alarm outputs using loop output devices. |
| Global Fire Outputs | 1 set of non-monitored changeover contacts (1A @ 24V dc) operating on any fire |
| Alarm Load | 600mA loop, 100mA per conventional alarm output |
| Fault Monitoring | Fully fault monitored to EN 54-2 & 4 |
| Fault Output | Single pole changeover contacts (1A rated @ 24V dc) |
| Auxiliary Output Supply | 24V dc fused at 150mA |
| Common Fire Output (fire station) | 24V dc fully monitored output (requires end of line module SF4165759) |
| Communications Interface | USB 2.0 (Type A male to Type B male connection lead required – 2 Metres maximum length) |
| Dimensions (mm) | 228(W) x 345(H) x 111(D) |
| Weight | 1.5kg (excluding batteries) |
| Applicable Standards | EN 54-2 : 1997 + A1 : 2006 EN 54-4 : 1998 + A1 + A2 |
Datasheet Clique Aqui